SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
249
Reference
5.31 Discharge Pipe Temperature Abnormality
5.31.1 Discharge Pipe Temperature Abnormality (4/5 HP Models)
Applicable
Models
RXQ4/5AR
Error Code
F3
Method of Error
Detection
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
The discharge pipe temperature rises to an abnormally high level.
The discharge pipe temperature rises suddenly.
Supposed
Causes
Defective discharge pipe thermistor (R2T)
Disconnection of discharge pipe thermistor (R2T)
Defective outdoor unit main PCB
Troubleshooting
CHECK 11
Refer to page 350.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
YES
YES
NO
NO
CHECK 11
Replace the outdoor
unit main PCB (A1P).
When the
unit stops operating
because of an error, is the discharge
pipe temperature higher than
120˚C?
Are the
discharge pipe thermistor
properties normal?
Pull the discharge pipe thermistor out from
the outdoor unit main PCB and then
measure the resistance with a multimeter.
Refrigerant shortage,
compressor failure,
refrigerant system failure, etc.
Replace the discharge
pipe thermistor (R2T).
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...