Check
SiAF332111E
348
Part 6 Service Diagnosis
6.9 Inverter-Related Error Codes
CHECK 9
Code
Name
Condition for determining error
Major cause
Compressor
current
L5
Instantaneous overcurrent
of compressor
• Inverter output current exceeds
A
(A) even instantaneously.
• Liquid sealing
• Defective compressor
• Defective inverter PCB
L8
Overcurrent of
compressor (Electronic
superheating protection
sensor)
• Compressor overload running
A current of
B
(A) or more continues
for a period of consecutive 5
seconds or that of
C
(A) or more
continues for a period of
consecutive 260 seconds.
• The inverter loses synchronization.
• Back-flow of compressor liquid
• Sudden changes in loads
• Disconnected compressor wiring
• Defective inverter PCB
Protection
device and
others
E5
Compressor lock
• The compressor is in the locked
status (does not rotate).
• Defective compressor
L1
Defective inverter PCB
• No output is given.
• Defective heavy current part of
compressor
L4
Radiation fin temperature
rise
• The radiation fin temperature
reaches
D
(°C) or more (while in
operation).
• Defective fan
• Running in overload for an extended
period of time
• Defective inverter PCB
L9
Defective startup of
compressor
• The compressor motor fails to start
up.
• Liquid sealing or defective
compressor
• Excessive oil or refrigerant
• Defective inverter PCB
LC
Transmission error
(between microcomputers
on the outdoor main PCB)
• No communications are carried
out across outdoor main PCB -
inverter PCB - fan PCB.
• Broken wire in communication line
• Defective outdoor main PCB
• Defective inverter PCB
• Defective fan PCB
P1
Imbalanced power supply
• Power supply voltages get
significantly imbalanced among
three phases.
• Power supply error (imbalanced
voltages of 2% or more)
• Defective inverter PCB
• Dead inverter PCB
P4
Defective radiation fin
thermistor
• The radiation fin thermistor gets
short circuited or open.
• Defective radiation fin thermistor
PJ
PCB mismatching
• Any PCB of specification different
from that of the product is
connected.
• PCB of different specification
mounted
U2
Power supply voltage
error
• The inverter power supply voltage
is high or low.
• Power supply error
• Defective inverter PCB
Model
A
(A)
B
(A)
C
(A)
D
(°C)
RXQ4AR
36.9
17.0
14.8
92
RXQ5AR
51.5
31.0
24.1
85
RXMQ10/12AR
59.1
33.5
27.6
87
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...