SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
305
5.58.3 Power Supply Insufficient or Instantaneous Abnormality (10/12 HP
Models)
Applicable
Models
RXMQ10/12AR
Error Code
U2
Method of Error
Detection
Error of voltage of main circuit capacitor built in the inverter and power supply voltage.
Error Decision
Conditions
When the voltage of main circuit capacitor built in the inverter and power supply voltage is less
than 320 V.
Supposed
Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor unit main PCB
Defective main circuit wiring
Defective compressor
Defective fan motor
Defective connection of signal cable
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the compressor.
Replace the fan motor.
YES
Failure of
above power supply.
Check the power condition.
(1) Is the power supply voltage 380 V ±10%?
(2) Is there phase loss or wrong wiring?
(3) Is the unbalanced power voltage less than 6 V?
Repair the failure.
YES
NO
NO
NO
YES
If the motor is
seriously damaged,
it is necessary to
replace the inverter
PCB (A3P).
Go to the next page.
A
Check
if the insulation
resistance of the
compressor is less
than 100 k
Ω.
Check
if the insulation
resistance of the fan
motor is less than
1 M
Ω.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...