Field Settings for Outdoor Unit (6/8 HP Models)
Part 5 Field Settings and Test Operation
147
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Power consumption
Rated
80%
40%
Forced thermostat OFF
(Fan operation)
60%
70%
Demand level 1
instructing
Power consumption set by
"Demand 1 level setting".
Demand level 2
instructing
Demand level 3
instructing
The power
consumption
during the
demand level 1
instructing can be
set with the
"Demand 1 level
setting".
("70% of rated
power
consumption" has
been set at
factory.)
The power consumption set with "Demand 1 level setting".
When the
"Normal demand
setting" is set to
ON ("OFF" has
been set at
factory.), the
power
consumption can
be set with the
"Demand 1 level
setting". ("70% of
rated power
consumption" has
been set at
factory.)
Power consumption
Rated
80%
70%
60%
The power consumption set with
"Demand 1 level setting".
Demand level
2 instructing
Demand level
3 instructing
The power
consumption can
be set with the
"Demand 1 level
setting". ("70% of
rated power
consumption" has
been set at
factory.)
During constant demand
operation, when the
external demand
instruction is received, the
instruction with higher
demand level has the
precedence.
Power consumption
Rated
Forced thermostat OFF
(Fan operation)
40%
60%
70%
80%
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...