Troubleshooting by Error Code
SiAF332111E
260
Part 6 Service Diagnosis
5.37 Outdoor Fan PCB Abnormality
Applicable
Models
RXMQ8AR
Error Code
H7-21
Method of Error
Detection
Detect according to values detected with current sensor.
Error Decision
Conditions
When the current sensor is abnormal.
Supposed
Causes
Disconnection/Short circuit in fan motor leads or disconnection of connector
Defective fan PCB
Troubleshooting
Replace the fan motor (M1F).
NO
YES
Replace the fan PCB (A4P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is
resistance
between Vcc-UVW
and between GND-UVW
of the fan motor lead in
balance?
Turn OFF the power supply
and wait for 10 minutes.