![background image](http://html1.mh-extra.com/html/daikin/vrv-s-rxmq10ary1/vrv-s-rxmq10ary1_service-manual_2459219225.webp)
SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
219
Troubleshooting
Properly connect the connector.
NO
YES
Is the X70A
connector on the indoor
unit PCB properly
connected?
Properly connect the connector.
NO
YES
Is the X12A
connector on the auto grille
control PCB properly
connected?
Replace the harness.
YES
Is the harness
disconnected?
NO
YES
NO
Remove the external factor.
YES
Is there any
external factor such as
noise?
Check the indoor unit PCB and
the auto grille control PCB.
NO
Is
"Auto grille
elevation operation"
displayed in the remote
controller menu?
Normal.
YES
Check the indoor unit PCB and
the auto grille control PCB.
NO
Can
the target unit be
selected?
Turn OFF the power once and turn
ON again. Then, start grille
operation with remote controller.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.