Capacity Range
Part 1 General Information
11
3. Capacity Range
3.1 Connection Ratio
3.2 Outdoor Unit Combinations
Type
Min. connection ratio
Max. connection ratio
Single outdoor units
50%
130%
Connection ratio =
Total capacity index of the indoor units
Capacity index of the outdoor units
Model
RXQ4ARV1
RXQ5ARV1
RXMQ6ARV1
RXMQ8ARY1
RXMQ10ARY1
RXMQ12ARY1
kW
11.2
14.0
16.0
22.4
28.0
33.5
HP
4
5
6
8
10
12
Capacity index
100
125
150
200
250
300
Total capacity
index of
connectable
indoor units
Combination (%)
50%
50
62.5
75
100
125
150
100%
100
125
150
200
250
300
130%
130
162.5
195
260
325
390
Maximum number of connectable indoor
units
6
8
9
13
16
19