Troubleshooting by Error Code
SiAF332111E
294
Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
CHECK 11
Refer to page 350.
CHECK 12
Refer to page 353.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
CHECK 12
CHECK 11
Is it cooling?
Is the low
pressure less or equal
to 0.25 MPa?
Is the
temperature
difference between the suction
pipe and the outdoor heat
exchanger greater
than 20˚C?
Is the resistance
measured from suction pipe
thermistor disconnected from
the outdoor unit main
PCB normal?
Is the voltage between
X18A pins (2) and (3) of outdoor unit
main PCB (A1P) less or equal to 1.0 VDC?
(Low pressure sensor output
voltage)
Is the low pressure
sensor normal?
Refrigerant shortage, closed
stop valve, or blocked cooling
system. Check the refrigerant
system.
Replace the outdoor unit main
PCB (A1P).
Replace the low pressure
sensor.
Replace the outdoor unit main
PCB (A1P).
Refrigerant shortage or blocked
cooling system. Check the
refrigerant system.
Replace the suction pipe
thermistor.
Replace the low pressure sensor.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...