Field Settings for Outdoor Unit (10/12 HP Models)
SiAF332111E
150
Part 5 Field Settings and Test Operation
In
Setting mode
and
Confirmation mode
operate according to
the following sequences.
Settings
Seven-segment display
SEG1
SEG2
SEG3
Setting
sequences
(1) Press the SET button (BS2) to set the
seven-segment display to any of the setting
items ((A) to (G)) listed in the table on the right.
(
1) Set outdoor unit low noise operation and
query through the external controller (optional
accessory) for cooling/heating selector operation
settings.
Refer to the optional accessories manual for
details.
(A) For selecting cooling/heating
mode (
1)
2
0
0
(B) For charging additional refrigerant
for operation
2
2
0
(C) For setting refrigerant
recycle/vacuum mode
2
2
1
(D) For setting night-time low noise
mode
2
2
2
(E) For setting external low noise
level (
1)
2
2
5
(F) For setting the demand level (
1)
2
3
0
(G) For external low noise demand
(
1)
2
1
2
(2) Press the RETURN button (BS3). (Displays the current set value)
Any of the displays in (3)
(3) Press the SET button (BS2) to set
the seven-segment display to any of
the setting items listed in the table on
the right.
For (A)
Cooling/heating mode switching of
individual units in various outdoor unit
systems
OFF
OFF
0
For
(B)(C)(G)
ON
OFF
OFF
1
OFF (Default)
OFF
OFF
0
For (D)
(
2)
OFF (Default)
OFF
OFF
0
Level 1
OFF
OFF
1
Level 2
OFF
OFF
2
Level 3
OFF
OFF
3
For (E)
(
2)
Level 1
OFF
OFF
1
Level 2 (Default)
OFF
OFF
2
Level 3
OFF
OFF
3
For (F)
(
2)
Level 1
OFF
OFF
1
Level 2
OFF
OFF
2
Level 3 (Default)
OFF
OFF
3
Level 4
OFF
OFF
4
Level 5
OFF
OFF
5
Level 6
OFF
OFF
6
Level 7
OFF
OFF
7
Level 8
OFF
OFF
8
(4) Press the RETURN button (BS3)
Verify the set value in (3)
The upper display stops
blinking and is turned ON.
(5) Press the RETURN button (BS3)
again
Operate according to the settings
2
0
0
(6) Press the MODE button (BS1)
Return to normal mode
OFF
OFF
OFF
Confirmation
sequences
(1) Press the SET button (BS2) to set
the seven-segment display to the
setting items ((H)/(J)) listed in the
table on the right.
(H) For low noise operation
1
0
1
(J) For operation demand
1
0
2
(2) Press the RETURN button (BS3).
(Displays the current set value)
During setting operation
OFF
OFF
1
During normal operation
OFF
OFF
0
1
1 2 3 4 5 6 7 8
2
3
Level
(
∗
2) Effects of level setting
Level
Noise level
(D) (E)
(F)
Low noise
(
∗
3) Effects of level setting
Power consumption Power-saving value
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...