Field Settings for Outdoor Unit (4/5 HP Models)
Part 5 Field Settings and Test Operation
111
2.2 Setting Mode and Monitor Mode
The following 3 modes can be changed over with the button switches on the PCB and you can
find the present mode by the status of the H1P indicator.
1.
Setting mode 1 (H1P OFF)
Initial status (normal): Also indicates during abnormal.
2.
Setting mode 2 (H1P ON)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
3.
Monitor mode (H1P blinks)
Used to check the program made in setting mode 2.
1 2
ON
OFF
DS1
H1P H3P
H5P H7P
H2P H4P H6P
MODE
(BS1)
SET
(BS2)
TEST
(BS4)
RESET
(BS5)
RETURN
(BS3)
Monitor mode
Setting mode 2
Setting mode 1
(Initial condition)
MODE
OFF
H1P
MODE
ON
H1P
H1P
Blinking
MODE
Press the
button.
RETURN (BS3)
Press the
button.
RETURN (BS3)
Press the
button.
RETURN (BS3)
Press the
button.
RETURN (BS3)
Press the
button.
RETURN (BS3)
Press the
button.
MODE (BS1)
Press the
button.
MODE (BS1)
Press the
MODE (BS1)
button for more
than 5 seconds.
Press the
MODE (BS1)
button.
Select a setting item with
the
SET (BS2)
button.
Select a check item with
the
SET (BS2)
button.
Select a setting condition
with the
SET (BS2)
button.
Setting condition
(Contents) display
Contents display
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...