Field Settings for Outdoor Unit (4/5 HP Models)
SiAF332111E
114
Part 5 Field Settings and Test Operation
The numbers in the No. column represent the number of times to press the
SET (BS2)
button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
2
Low noise / demand
address
1
Cool / heat
unified address
k
h
h
h
h
k
h
k
h
h
h
h
h
k
Address
0
k h h h h h h
∗
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
(
(
31
k h k k k k k
Address
0
k h h h h h h
∗
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
31
k h k k k k k
3
Test operation
settings
k
h
h
h
h
k
k
Test operation : OFF
k h h h h h k
Test operation : ON
k h h h h k h
∗
5
Indoor unit forced
fan H
k
h
h
h
k
h
k
Normal operation
k h h h h h k
∗
Indoor forced fan H
k h h h h k h
6
Indoor unit forced
operation
k
h
h
h
k
k
h
Normal operation
k h h h h h k
∗
Indoor forced operation
k h h h h k h
8
Te setting
k
h
h
k
h
h
h
High
k h h h k h h
Normal (factory setting)
k h h h h k h
∗
Low
k h h h h h k
12
External low noise /
demand setting
k
h
h
k
k
h
h
External low noise/demand:
NO
k h h h h h k
∗
External low noise/demand:
YES
k h h h h k h
13 AIRNET address
k
h
h
k
k
h
k
Address
0
k h h h h h h
∗
Binary number
1
k h h h h h k
~
)
s
t
i
g
i
d
6
(
63
k k k k k k k
20
Additional refrigerant
charge operation
setting
k
h
k
h
k
h
h
Refrigerant charging: OFF
k h h h h h k
∗
Refrigerant charging: ON
k h h h h k h
21
Refrigerant recovery /
vacuuming mode
setting
k
h
k
h
k
h
k
Refrigerant recovery /
vacuuming: OFF
k h h h h h k
∗
Refrigerant recovery /
vacuuming: ON
k h h h h k h
22
Night-time low noise
setting
k
h
k
h
k
k
h
OFF
k h h h h h h
∗
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
Level 3 (outdoor fan with 4 step or lower)
k h h h h k k
25
Setting of low noise
level
k
h
k
k
h
h
k
Level 1 (outdoor fan with 6 step or lower)
k h h h h h k
Level 2 (outdoor fan with 5 step or lower)
k h h h h k h
∗
Level 3 (outdoor fan with 4 step or lower)
k h h h k h h
26
Night-time low noise
operation start
setting
k
h
k
k
h
k
h
About 20:00
k h h h h h k
About 22:00 (factory setting)
k h h h h k h
∗
About 24:00
k h h h k h h
27
Night-time low noise
operation end setting
k
h
k
k
h
k
k
About 6:00
k h h h h h k
About 7:00
k h h h h k h
About 8:00 (factory setting)
k h h h k h h
∗
28
Power transistor
check mode
k
h
k
k
k
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
29
Capacity
precedence setting
k
h
k
k
k
h
k
OFF
k h h h h h k
∗
ON
k h h h h k h
30 Demand setting 1
k
h
k
k
k
k
h
60% demand
k h h h h h k
70% demand
k h h h h k h
∗
80% demand
k h h h k h h
32
Constant demand
setting
k
k
h
h
h
h
h
OFF
k h h h h h k
∗
ON
k h h h h k h
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...