SiAF332111E
Test Operation (4/5/10/12 HP Models)
Part 5 Field Settings and Test Operation
163
Set the BS buttons (BS1~5) after making sure the service monitoring lamp has been
ON.
For setting method, see the
Service Precautions
label attached to the front panel of
the outdoor unit. (Be sure to keep a record of the setting items to the
Service
Precautions
label.)
Don't touch the changeover switches (DS1-1) while setting them. Doing so may result
in malfunction.
(7) Check whether the gas side and liquid side stop valves have been opened. Open them if
they are closed.
(8) Press the
TEST (BS4)
button for 5 seconds or more to perform test operation. See
About
test operation
on the
Service Precautions
label for details.
Ask other installers to perform test operation or attach the front panel before having to
leave the outdoor unit working alone.
Test operation is automatically stopped after about 30 minutes (maximum 1 hour)
operation. (Perform checks of fault wiring, closed stop valves & refrigerant charging
and auto determination of piping length.)
After test operation is completed, if there is no error code on the display of the remote
controller, the unit can perform normal operation 3 minutes later.
The display of the remote controller indicates symbol of test operation during this
operation.
(9) Be sure to attach the front panel of the outdoor unit after test operation is completed.
About test operation
If the system is started about 12 minutes later after the indoor and outdoor units opened, the
compressor will not operate and H2P will light up.
Before operating, always check whether the symbols indicated on the LED display are those
in the table under
Powering ON to Test Operation
.
In order to ensure uniform refrigerant distribution, it may take up to around 10 minutes for the
compressor to start up after the unit starting operation. This is not an error.
Meaning of operation check is not to check individual indoor unit. After completing operation
check, operate the system normally with the remote controller.
Test operation cannot be performed when the unit is in other modes such as refrigerant
recycling mode.
Never perform test operation with discharge pipe thermistor (R2T), suction pipe thermistor
(R3T) and pressure sensor (S1NPH, S1NPL) removed. Doing so will result in compressor
damaged.
Power supply has been turned on for outdoor unit, be careful to avoid electric shock.
Caution
Operation with the stop valve closed may result in compressor malfunction.
Caution
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...