Field Settings for Indoor Unit
SiAF332111E
108
Part 5 Field Settings and Test Operation
1.5 Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information on the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor
is connected)
Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller
only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...