Field Settings for Outdoor Unit (4/5 HP Models)
SiAF332111E
118
Part 5 Field Settings and Test Operation
2.3.2 Demand Operation
By connecting the external contact input to the demand input of the external control adaptor for
outdoor unit (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
When the constant demand operation is carried out. (Use of the external control adaptor
for outdoor unit is not required.)
1. While in setting mode 2, set the item 2-32 (Constant demand setting) to ON.
2. While in setting mode 2, select a demand 1 level for the item 2-30.
Set item
Condition
Content
Demand 1
Level 1
The compressor operates at 60% or less of rating.
Level 2
The compressor operates at 70% or less of rating.
Level 3
The compressor operates at 80% or less of rating.
The power consumption set with "Demand 1 level setting".
When the
"Normal demand
setting" is set to
ON ("OFF" has
been set at
factory.), the
power
consumption can
be set with the
"Demand 1 level
setting". ("70% of
rated power
consumption" has
been set at
factory.)
Power consumption
Rated
80%
70%
60%
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...