SiAF332111E
Troubleshooting by Error Code
Part 6 Service Diagnosis
229
Note(s)
5.21 Remote Controller Thermistor Abnormality
Applicable
Models
All indoor unit models
Error Code
CJ
Method of Error
Detection
Error detection is carried out by the temperature detected by the remote controller thermistor.
Error Decision
Conditions
When the remote controller thermistor becomes disconnected or shorted while the unit is
running.
Error code is displayed but the system operates continuously.
Supposed
Causes
Defective remote controller thermistor
Defective remote controller PCB
Troubleshooting
1: How to delete “history of error codes”.
Press the
ON/OFF
button for 4 seconds and more while the error code is displayed in the
inspection mode.
Clear the error code history.
(While in inspection mode,
press and hold the
ON/OFF
button for a period of 4
seconds or more.)
YES
Is
CJ
displayed on the remote
controller?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Replace the remote
controller.
External factor other than
equipment error.
(for example, noise etc.)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...