Part 6 Service Diagnosis
345
6.6 Refrigerant Overcharge Check
CHECK 6
In case of
VRV
systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgment, refer to the information below.
Diagnosis of refrigerant overcharge
1. High pressure rises. Consequently, overload control is conducted to cause insufficient
cooling capacity.
2. The superheating degree of suction gas lowers (or wet operation is performed).
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
3. The subcooling degree of condensate rises.
Cooling
High pressure
Low pressure
Frequency
High pressure
gradually rises with
increase in
frequency.
Subcooling degree
becomes higher.
(Liquid connection
pipe temperature
lowers.)
Low pressure rises due
to decreased
compressor output.
Higher degree of overcharge
(Degree of overcharge)
Proper amount
To maintain low pressure, frequency
increases under the capacity
control.
Frequency comes to
the minimum level.
High pressure
dropping control
(Low pressure is
maintained at a
constant level.)
Summary of Contents for VRV S RXMQ10ARY1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...