Troubleshooting by Indication on the Remote Controller
ESIE09-08A
174
Troubleshooting
3.23
“F3”
Outdoor Unit: Abnormal Discharge Pipe Temperature
Remote Control
Display
F3
Applicable Models
ER*Q 011~016*
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe temperature sensor.
Malfunction
Decision Conditions
When the discharge pipe temperature rises to an abnormally high level
When the discharge pipe temperature rises suddenly
Supposed Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PC board
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P251.
(V3068)
Caution
Be sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
Discharge
pipe temperature is
120°C or higher when the unit
stop by malfunction.
Pull out the discharge pipe
thermistor from the outdoor PC
board, and then make
measurement of resistance using
a multiple meter.
Are the
characteristics of the
discharge pipe thermistor
normal?
(3.5~400K
Ω
)
*
Replace outdoor unit PC board
(A1P).
Replace the discharge pipe
thermistor.
NO
NO
Refrigerant shortage, compression
defect, etc. Defect of the refrigerant
system.
YES
YES
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...