ESIE09-08A
Basic Control
Function
57
2.3
Electronic Expansion Valve PI Control R-410A
circuit
Main Electronic Expansion Valve EV1 Control - Outdoor Unit
Carries out the electronic expansion valve (Y1E) PI control to maintain the evaporator outlet superheated
degree (SH) at constant during heating operation to make maximum use of the outdoor unit heat
exchanger (evaporator).
The optimum initial value of the evaporator outlet superheated degree is 3°C, but varies depending on the
discharge pipe superheated degree of inverter compressor.
Subcooling Electronic Expansion Valve EV3 Control - Outdoor Unit
Makes PI control of the electronic expansion valve (Y3E) to keep the superheated degree
(SH)
of the
outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger.
Electronic Expansion Valve K1E Control - Indoor Unit
Carries out the electronic expansion valve (K1E) PI control to maintain the condensor outlet subcooled
degree (SC) at constant during heating operation to make maximum use of the indoor unit heat exchanger
(condensor).
2.4
Electronic Expansion Valve PI Control R-134a
circuit
Electronic Expansion Valve K2E Control - Indoor Unit
Carries out the electronic expansion valve (K1E) PI control to maintain the condensor outlet subcooled
degree (SC) at constant during heating operation to make maximum use of the indoor unit heat exchanger
(condensor).
SH = Ts1 - Te
SH : Evaporator outlet superheated degree (°C)
Ts1 : Suction pipe temperature detected by thermistor R3T
(°C)
Te : Low pressure equivalent saturation temperature (°C)
SH = Tsh
- Te
SH : Outlet superheated degree of evaporator (
C)
Tsh : Suction pipe temperature detected with the
thermistor R4T (
C)
Te : Low pressure equivalent saturation temperature (
C)
SC = Tc - R3T
SC = Tc - R7T
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...