ESIE09-08A
Field Setting
Test Operation
107
[A] Option setup
[A-01]
Current limitation
The indoor unit current is limited, the outdoor unit is slave and will also reduce its power
consumption consequentially. However transient conditions with higher power consumption are
possible.
[A-02]
Temperature difference for leaving and returning water
The unit is designed to support radiator operation. The advised leaving water temperature (set by the
remote controller) for radiators is 65°C. In such a case the unit will be controlled to realize a
temperature difference (
Δ
T) of 10°C, which means that the returning water to the unit is around 55°C.
Depending on the installed application (radiators, fan coil units, ...) or situation, it can be required to
change the
Δ
T. This can be done by changing field setting [A-02].
[A-03]
Multi set point 1 temperature.
[A-04]
Multi set point 2 temperature.
Notes :
1. When temperature reducing devices are installed, the system can be configured to use multi set points,
also the demand PCB (option) is needed.
2. The selected values for multiple set point should be lower than the value from remote controller
(reference temperature) or domestic hot water temperature (pattern A).
3. Daikin does not offer any temperature reducing device (TRD). This system (multi set point control)
only provides the possibility to use multi set point. It’s than also the installers responsibility to make
sure that the whole system is operating well.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
A
Option setup
00
Current limitation
0
0~2
1
—
02
Set point: required temperature difference for
leaving and returning water
10
5~15
1
°C
03
Set point: multiple set point 1 required
temperature value
35
25~80
1
°C
04
Set point: multiple set point 2 required
temperature value
65
25~80
1
°C
Settting
V1
Y1
[A-01]=0 (default)
23 A
13 A
[A-01]=1
18.4 A
10.4 A
[A-02]=2
15 A
8.5 A
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...