ESIE09-08A
Symptom-based Troubleshooting
Troubleshooting
129
1. Symptom-based Troubleshooting
Symptom
Supposed Cause
Countermeasure
1
The system does not start operation at all.
Blowout of fuse(s)
Turn Off the power supply and then
replace the fuse(s).
Cutout of breaker(s)
• If the knob of any breaker is in its
OFF position, turn ON the power
supply.
• If the knob of any circuit breaker is
in its tripped position, do not turn
ON the power supply.
Power failure
After the power failure is reset,
restart the system.
Open phase in power supply cable
Check power supply. After that,
properly connect the power supply
cable, and then turn ON the power
supply.
2
The system starts operation but makes an immediate
stop.
Blocked air inlet or outlet of outdoor
unit
Remove obstacle(s).
3
The unit is turned on but the unit is not heating as
expected.
The temperature setting is not
correct.
Check the controller set point +
settings (room + water).
Capacity shortage.
Check if the cooling fans at the rear
of the switch box are working
properly.
The water volume in the installation
is too low.
Make sure that the water volume in
the installation is above the minimum
required value.
Check if there is no bypass of the
water circuit.
The water flow is too low.
• Check that all shut-off valves of
the water circuit are completely
open.
• Check if the water filter needs
cleaning.
• Make sure there is no air in the
system (purge air).
• Make sure that the expansion
vessel is not broken.
• Check the water pressure on the
manometer > 0,3 bar.
4
The system does
not operate.
The system stops and
immediately restarts operation.
If the OPERATION lamp on the
remote control turns ON, the system
will be normal. These symptoms
indicate that the system is controlled
so as not to put unreasonable loads on
the system.
Normal operation. The system will
automatically start operation after a
lapse of five minutes.
The remote control displays
"UNDER CENTRALIZED
CONTROL", which blinks for a
period of several seconds when
the OPERATION button is
depressed.
The system is controlled with
centralized control.
Recovery/vacuum mode is active
(higher priority mode).
The system stops immediately
after turning ON the power
supply.
The system is in preparation mode of
micro computer operation.
Wait for a period of approximately
one minute.
5
The system makes
intermittent stops.
The remote control displays
malfunction codes "U4" and
"U5", and the system stops but
restarts after a lapse of several
minutes.
The system stops due to an
interruption in communication
between units caused by electrical
noises coming from equipment other
than air conditioners.
Remove causes of electrical noises.
If these causes are removed, the
system will automatically restart
operation.
ON
OFF
Knob
Tripped
Circuit breaker
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...