Field Setting
ESIE09-08A
106
Test Operation
[9] Automatic temperature compensation
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be used
as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then used for
controlling the system and will be displayed in the temperature read-out mode.
[9-00]
Leaving water temperature compensation value
[9-01]
Domestic hot water tank compensation value
[9-02]
Thermo ON/OFF admission
By changing this value the operation range for space heating operation can be modified.
If the ambient temperature becomes higher than (24°C + the value of [9-02]) no space heating is
possible.
Space heating can be requested as long as the ambient temperature is lower than (20°C + the value of
[9-02]).
Example:
[9-02] = –2°C
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
9
Automatic temperature compensation
00
Leaving water temperature compensation value
0
–5~5
0.5
°C
01
Domestic hot water tank compensation value
0
–5~5
0.5
°C
02
Thermo ON/OFF admission
0
–5~5
0.5
°C
A
No space heating operation possible
B
Request for space heating possible
C
Hysteresis area
T
Ambient temperature
T
20
°
C–2
°
C =
18
°
C
24
°
C–2
°
C =
22
°
C
A
B
C
C
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...