[B] Domestic hot water set points
The reheat mode will prevent the domestic hot water from cooling down lower than a certain temperature.
When enabled the indoor unit will deliver hot water to the domestic hot water tank if the reheat minimum
value is reached. The domestic water heating will continue until the reheat maximum temperature is
reached. In this way always a minimum of domestic hot water is available.
[b-00]
Set point: reheat minimum temperature (see figure below).
[b-01]
Set point: reheat maximum temperature (see figure below).
Notes :
1. Remark that the
w
icon will only be blinking during effective automatic storage operation. Presence
of the permanently lit
w
icon does not mean that automatic storage is enabled, but only means that
reheat is enabled.
2. During operation it is always possible to cancel the operation by pushing the
w
button once.
3. Pushing the
y
button has no influence on the domestic water heating. Domestic hot water heating
is only switched on or off by means of the
w
button and/or disabling the storage schedule timer.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
B
Domestic hot water set points
00
Set point: reheat minimum temperature
35
35~65
1
°C
01
Set point: reheat maximum temperature
45
35~75
1
°C
02
Status: weather dependent domestic water heating
1 (ON)
0/1
—
—
03
Set point: storage temperature
70
45~75
1
°C
04
Automatic maximum domestic hot water storage
temperature
70
55~75
1
°C
A
Storage operation (if activated)
B
Reheat operation (if activated)
C
Disinfection operation (if activated)
Field settings
D
Disinfection operation temperature [5-00] (e.g. 70°C)
E
Hot water storage temperature [b-03] (e.g. 60°C)
F
Reheat maximum water temperature [b-01] (e.g. 45°C)
G
Reheat minimum water temperature [b-00] (e.g. 35°C)
t
Time
T
Domestic hot water tank temperature
A
B
C
D
E
F
G
T
t
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...