Field Setting
ESIE09-08A
100
Test Operation
[4] Disinfection function
This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a
specific temperature.
Note :
If a domestic hot water tank is installed, the disinfection function is enabled by default.
[4-00]
Status: defines whether the disinfection function is turned ON (1) or OFF (0).
[4-01]
Operation interval: day of the week at which the domestic water should be heated.
[4-02]
Start time: time at which the disinfection operation is started.
Even if all schedule timers are de-activated and there is no reheat function active, the disinfection
function will operate if a domestic hot water tank is installed and field setting [4-00] is set to ON.
The disinfection function field settings must be configured by the installer according to national and local
regulations.
Refer to “[5] Automatic setback and disinfection set point” on page 102 for temperature set points.
Note :
This function may be disabled if the set point storage temperature is higher than the disinfection set point.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
4
Disinfection function
00
Status: disinfection operation
1 (ON)
0/1
—
—
01
Disinfection operation day selection
Fri
Mon~Sun
—
—
02
Disinfection operation start time
23:00
0:00~23:00
1:00
hour
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...