[3] Weather dependent set point
When weather dependent operation is active, the leaving water temperature is determined automatically
depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice
versa. The unit has a floating set point. Activating this operation will result in a lower power consumption
than use with a manually fixed leaving water set point.
During weather dependent operation, the user has the possibility to shift up or down the target water
temperature by a maximum of 5°C. This "Shift value" is the temperature difference between the
temperature set point calculated by the controller and the real set point. E.g. a positive shift value means
that the real temperature set point will be higher than the calculated set point.
It is advised to use the weather dependent set point because it adjusts the water temperature to the actual
needs for space heating. It will prevent the unit from switching too much between thermo ON operation
and thermo OFF operation when using the remote controller room thermostat or external room
thermostat.
Note :
During this operation, instead of showing the water temperature set point, the controller shows the shift
value which can be set by the user.
[3-00]
Low ambient temperature (Lo_A): low outdoor temperature.
[3-01]
High ambient temperature (Hi_A): high outdoor temperature.
[3-02]
Set point at low ambient temperature (Lo_Ti): the target outgoing water temperature when the
outdoor temperature equals or drops below the low ambient temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for colder outdoor temperatures (i.e. Lo_A)
warmer water is required.
[3-03]
Set point at high ambient temperature (Hi_Ti): the target outgoing water temperature when the
outdoor temperature equals or rises above the high ambient temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e.
Hi_A) less warm water suffices.
Note :
If by mistake the value of [3-03] is set higher than the value of [3-02], the value of [3-03] will always be
used.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
3
Weather dependent set point
00
Low ambient temperature (Lo_A)
–10
–20~5
1
°C
01
High ambient temperature (Hi_A)
15
10~20
1
°C
02
Set point at low ambient temperature (Lo_Ti)
70
25~80
1
°C
03
Set point at high ambient temperature (Hi_Ti)
45
25~80
1
°C
T
t
Target water temperature
T
A
Ambient (outdoor) temperature
= Shift value
Lo_Ti
Lo_A
Hi_A
T
A
T
t
+ 05
00
– 05
Hi_Ti
Shift value
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...