Troubleshooting by Indication on the Remote Controller
ESIE09-08A
170
Troubleshooting
3.21
“E9”
Outdoor Unit: Malfunction of Moving Part of Electronic
Expansion Valve
Remote Control
Display
E9
Applicable Models
ER*Q 011~016*
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision Conditions
Error is generated under no common power supply when the power is on.
Supposed Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting
(V3067)
YES
Caution
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X21A and X22A
of outdoor unit PC
board (A1P)
The
connecting cable is
short-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board
(A1P).
NO
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
YES
YES
YES
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...