Test Operation
ESIE09-08A
82
Test Operation
1.3.1
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases
into the atmosphere.
Refrigerant type:
R-410A
GWP
(1)
value:
1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged in the field and
+
the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of
the service cover).
1.3.2
Procedures for adding refrigerant
How to connect the tank?
Caution
Automatic refrigerant charging is NOT POSSIBLE.
Make sure to turn ON the power 6 hours before starting the operation. This is necessary to warm the
crankcase by the electric heater.
total refrigerant charge
outdoor unit
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
factory refrigerant charge of the product:
see unit name plate
additional refrigerant amount charged
in the field
refrigerant cylinder and
manifold for charging
Contains fluorinated greenhouse gases covered by the Kyoto Protocol
1
Liquid line stop valve
2
Gas line stop valve
3
To indoor unit
4
Valve A
5
R-410A tank
6
Measuring instrument
7
Pipe fixing plate
3
5
6
1 2
4
3
5
6
1 2
7
4
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...