ESIE09-08A
Field Setting
Test Operation
103
[7] Option setup
[7-00]
Bottom plate heater option
An optional bottom plate heater can be installed in your outdoor unit. In case an ERRQ* outdoor unit
(special model with freeze-up countermeasures) is installed, the unit will have the bottom plate heater
already standard installed.
If the bottom plate heater is installed, its operation must be enabled by field setting. Default [7-00] = 0
which means no bottom plate heater is installed. Set [7-00] to 1 if the bottom plate heater is installed.
[7-02]
Select multiple set point pattern A or B
Multi set point control according pattern A
During normal operation, domestic water heating and space heating modes are separated and
activated intermittent to fulfil a simultaneous request. Therefor multiple set point pattern A can be
configured to allow simultaneous domestic water and space heating without intermission.
Multi set point control according pattern B
The basic setup of multiple set point pattern B is the same as a normal classic design, so AGAIN
no domestic water heating and space heating is possible simultaneously. Multiple set point pattern
B is focussed on space heating operation and allows using multiple water set points in
combination with the remote controller or external room thermostat. The configuration of pattern
B allows space heating set points and the domestic hot water set point.
[7-03]
Activation for multiple set point 1
[7-04]
Activation for multiple set point 2
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
7
Option setup
00
Optional bottom plate heater installed
0 (OFF)
0/1
—
—
02
Multiple set point pattern
0 (A)
0/1
—
—
03
Multiple set point 1
0 (OFF)
0/1
—
—
04
Multiple set point 2
0 (OFF)
0/1
—
—
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...