Troubleshooting by Indication on the Remote Controller
Troubleshooting
165
:
Refer to information on page 219.
NO
YES
NO
YES
NO
YES
CHECK 2
Is the
stop valve
open?
Open the stop valve.
Mount a pressure gauge on the low-pressure service port.
Connect the Service Tool.
Reset the operation using the remote control, and then restart
the operation.
Are the
characteristics of
the low pressure sensor
normal? (See
*1.)
Replace the low pressure sensor.
Is the
pressure
detected with the PC
board normal?
(See *2.)
Replace the control PC board (A4P).
.
·
The low pressure sensor is normal, and the pressure
detected with the PC board is also normal.
·
The low pressure has really become low.
Refer to “remove the causes by which the low
pressure has become low”.
*1: Make a comparison between the voltage of the pressure sensor (*4) and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure.)
*2: Make a comparison between the low pressure value checked with the Service Tool
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
Caution
Be sure to turn off power switch before connecting or disconnecting
connector, otherwise parts may be damaged.
+5V
(4)
(3)
(2)
(1)
Connector for low pressure sensor
Micro controller
A/D input
Make measurement of DC voltage between these wires. (*4)
(Blue)
Red
Black
White
Low
pressure
sensor
Check No.2
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...