Specifications
ESIE09-08A
10
Specifications
Electrical Specifications
Power Supply
Name
EKHBRD(011/014/016)AA/AB/
ACV1
EKHBRD(011/014/016)AA/AB/
ACY1
11
14
16
11
14
16
Phase
1~
3~
Frequency
Hz
50
50
Voltage
V
220-240
380-415
Voltage Range
Minimum
V
198
342
Maximum
V
254
440
Current
Z-max
(2)
Ω
0,34
0,32
0,32
-
Minimum Ssc
(3)
value
kVa
Equipment complying with EN/IEC
61000-3-12
(1)
-
Maximum
running Current
Heating
A
22,5
23,8
23,8
12,5
Recommended fuses
A
25
16
Wiring
Connections
For power
supply
Quantity
2G
4G
Wire type
Note
(4)
Note
(4)
For power
supply
(5)
Quantity
2G + 2G
4G + 2G
Wire type
Note
(4)
Note
(4)
For connection
with outdoor
unit
Quantity
2
Remark
F1+F2
Power Supply Intake
Both indoor unit and outdoor unit
Notes
(1): European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems
with input current > 16A and
75A per phase
(2): In accordance with EN/IEC 61000-3-11
(6)
, it may be necessary to consult the distribution network operator to ensure that the equipment is
connected only to a supply with Zsys
(7)
Zmax
(3): Short-circuit power
(4): Select diameter and type according to national and local regulations
(5): In case of benefit kWh rate power supply installations
(6): European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current
75A
(7): System impedance
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...