ESIE09-08A
Field Setting
Test Operation
97
[1] Automatic storage timing for domestic water heating
In this mode, the indoor unit will deliver hot water to the domestic hot water tank based on the daily fixed
pattern. This mode will continue until storage temperature is reached, no times are involved.
Automatic storage is the advised domestic hot water mode. In this mode water heats up during the night
(when space heating requirements are lower) until the storage set point. The heated water is stored in the
domestic hot water tank at a higher temperature so it can fulfil the domestic hot water requirements
throughout the day.
The storage temperature set point and timing are field settings.
[1-00]
Status: defines whether the domestic water heating (storage mode) during night is enabled (1)
or not (0).
[1-01]
Start time: time of the night at which the domestic water should be heated. The ending time
will variate for each system.
[1-02]
Status: defines whether the domestic water heating (storage mode) during daytime is enabled
(1) or not (0).
[1-03]
Start time: time of the day at which the domestic water should be heated. The ending time will
variate for each system.
Notes :
1. Make sure the domestic hot water is only heated up to the domestic hot water temperature you
require.
Start with a low domestic hot water storage temperature set point, and only increase if you feel that
the domestic hot water supply temperature is not sufficient for your needs (this depends on your water
using pattern).
2. Make sure the domestic hot water is not heated unnecessary. Start with activating automatic storage
during night (default setting). If it seems that the domestic hot water night storage operation is not
sufficient for your needs, an additional storage during daytime can be set.
3. For energy-saving purposes, it is advised to enable the weather dependent domestic water heating.
Refer to setting “[b-02] Status: defines whether the weather dependent domestic water heating is
turned ON (1) or OFF (0).” on page 110.
4. Manual storage is possible: to activate push 5 seconds on the
w
button. The
w
icon starts to blink,
the water will be heated up till storage set point (one time action). It can also be stopped manually by
pushing the
w
button.
5. Be aware that despite the automatic storage is a pre-programmed schedule timer, it is only active
when the schedule timer is enabled. This means that you have to push the
rp
button and confirm that
the
p
is displayed to make sure that the automatic storage will operate.
Refer to "[b] Domestic hot water set points" for temperature set points.
First
code
Second
code
Setting name
Default
value
Range
Step
Unit
1
Automatic storage timing for domestic water heating
00
Status: night time storage
1 (ON)
0/1
—
—
01
Night time storage start time
1:00
0:00~23:00
1:00
hour
02
Status: day time storage
0 (OFF)
0/1
—
—
03
Day time storage start time
15:00
0:00~23:00
1:00
hour
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...