Field Setting
Test Operation
109
[b-02]
Status: defines whether the weather dependent domestic water heating is turned ON (1) or OFF
(0).
If enabled, the storage set point will be set weather dependent.
In case of a higher ambient temperature (e.g. during summertime), the cold supply water to the
mixing tap (e.g. shower, bath) will also have a higher temperature. This makes that the temperature of
the hot water from the domestic hot water tank may be lower to reach the same water mixing
temperature from the shower or bath mixing tap. In this way, with a lower domestic hot water tank
temperature setting the comfort level can be kept the same but with a lower energy consumption.
(*) For EKHBRD*AA: Fixed at 70°C
For EKHBRD*AB/AC: [b-04]
Note :
The temperatures for weather dependent domestic water heating (see figure) are fixed and can not be
changed.
[b-03]
Set point: storage temperature (see figure above)
Note :
If weather dependent domestic water heating is enabled [b-02], the storage temperature will be set
automatically and the field setting [b-03] will be of no importance.
[b-04]
For EKHBRD*AA: Not applicable.
For EKHBRD*AB/AC: Automatic maxium domestic hot water storage temperature: default=70°C.
A
Ambient temperature
T
Domestic hot water storage temperature
T
A
70
°
C
55
°
C
15
°
C
25
°
C
[b-04] (*)
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...