Troubleshooting by Indication on the Remote Controller
ESIE09-08A
166
Troubleshooting
3.18
“E5”
Outdoor Unit: Inverter Compressor Motor Lock
Remote Control
Display
E5
Applicable Models
ER*Q 011~016*
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-current
waveform.
Malfunction
Decision Conditions
This malfunction will be output when the inverter compressor motor does not start up even in forced
startup mode.
Supposed Causes
Compressor lock
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.
Troubleshooting
Check the installation
conditions.
Is
the stop valve
open?
NO
Is the UVW wiring
normal?
NO
NO
NO
NO
Is high
differential pressure starting?
(0.5MPa or more)
YES
YES
YES
Check and see
whether compressor is
short-circuited or
ground.
YES
YES
Are
inverter output
voltages the same for 3
phases?
Does low or
high pressure vary
even instantaneously when
restarting compressor?
YES
Caution
Be sure to turn off power switch before connect or disconnect connector, or
parts damage may be occurred.
Open the stop valve.
Connect correctly.
Remedy the cause.
Replace the compressor.
Replace the inverter PC board
Assy (A2P).
Replace the compressor.
(V2793)
NO
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...