Outline of Control (Indoor Unit)
ESIE09-08A
76
Function
2. Storage operation
When requesting space heating and domestic water heating (storage) at the same time, this involves
that the minimum reheat temperature is reached (setting [b-00]) during space heating operation. The
3-way valve will switch over to the domestic hot water side, then the domestic water will be heated,
but as soon as the room temperature drops 3°C from set point (smart logic), the 3-way valve will go to
original position and start space heating till 0.5°C above set point, then the 3-way valve will switch
over to the domestic hot water side and then the domestic water will be heated again till storage set
point.
Remark:
a. The minimum operation time is only valid when room temperature is more than 3°C lower as set point
and set point J is reached.
b. The maximum operation time is only valid when room temperature is more than 0.5°C lower as set point
and set point J is reached.
A
Operation
Space heating
Domestic water heating
B
Domestic hot water storage thermo-on request
C
Domestic hot water tank temperature
D
Room temperature thermo-on request
E
Remote controller room temperature
F
Domestic hot water lower limit temperature
G
Domestic hot water upper limit temperature (maximum possible storage temperature) [b-03]
J
Domestic hot water reheat maximum temperature [b-01]
K
Remote controller thermostat set point
M
Simultaneous demand
N
ONLY domestic hot water request
R
Point where space heating gets priority
ON
ON
OFF
OFF
1
Minimum operation time for domestic water heating (initial 10 minutes [d-00])
(a)
2
Maximum operation time for domestic water heating (initial 30 minutes [d-01])
(b)
3
Interval minimum stop time for domestic water heating (initial 15 minutes [d-02])
N=4
No simultaneous operation
5
Timers for domestic water heating start
6
Timer for space heating start
A
M
R
N
B
C
J
K
75°C
35°C
–3.0°C
–0.5°C
+0.5°C
ON
G
F
OFF
D
E
ON
OFF
1
3
2
4
6
5
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...