Troubleshooting by Remote Control
ESIE09-08A
138
Troubleshooting
Malfunction code indication by outdoor unit PC board
<Selection of setting item>
<Monitor mode>
<Confirmation of malfunction 1>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
Detail
description
on next
page.
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Contents of malfunction
Malfunction
code
In-phase malfunction of DIII Net
Detection of DIII Net
E1
Abnormal discharge pressure
HPS activated
E3
Abnormal suction pressure
Abnormal Pe
E4
Compressor lock
Detection of INV compressor lock
E5
Over load, over current,
abnormal lock of outdoor unit fan motor
Detection of DC fan 1 motor lock
E7
Detection of DC fan 2 motor lock
Malfunction of electronic expansion valve
EV1
E9
EV3
Faulty sensor of outdoor air temperature
Faulty Ta sensor (short)
H9
Abnormal discharge pipe temperature
Abnormal Td
F3
Abnormal heat exchanger temperature
Refrigerant over charge
F6
Faulty sensor of discharge pipe
temperature
Faulty Tdi sensor (short)
J3
Faulty sensor of suction pipe temperature
Faulty Ts1 sensor (short)
J5
Faulty Ts2 sensor (short)
Faulty sensor of heat exchanger
temperature
Faulty Tb sensor (short)
J6
Malfunction of the liquid pipe temperature
sensor
Faulty TI sensor (short)
J7
Faulty sensor of subcool heat exchanger
temperature
Faulty Tsh sensor (short)
J9
Faulty sensor of discharge pressure
Faulty Pc sensor (short)
JA
Faulty sensor of suction pressure
Faulty Pe sensor (short)
JC
Faulty Inverter PC board
Faulty IPM
L1
Abnormal Current sensor offset
Abnormal IGBT
Faulty Current sensor
Abnormal SP-PAM over-voltage
Inverter radiation fin temperature rising
Over heating of inverter radiation fin temperature
L4
DC output over current
Inverter instantaneous over current
L5
Electronic thermal
Electronic thermal switch 1
L8
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Limit time)
Stall prevention (Current increasing)
L9
Stall prevention (Faulty start up)
Abnormal wave form in startup
Out-of-step
Transmission error between inverter and
outdoor unit
Inverter transmission error
LC
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...