Troubleshooting by Indication on the Remote Controller
Troubleshooting
211
Troubleshooting
: Refer to information on P221.
(V3187)
Caution
Be sure to turn off power switch before connecting or disconnecting
connector, otherwise parts may be damaged.
Is
indoor -
outdoor unit
transmission wiring
normal?
Repair the broken wires, and
then restart operation.
Replace the fuse.
Fix the indoor/outdoor unit
transmission wiring.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
Replace the outdoor unit PC
board (A1P).
YES
YES
NO
YES
Replace the indoor unit PC
board (A1P).
Fix the indoor/outdoor unit
transmission wiring.
YES
NO
NO
YES
Has
the indoor
or outdoor unit
PC board been
replaced, or has the indoor -
outdoor unit transmission
wiring been
modified?
Indoor unit
remote controller
displays “U4”
NO
Outdoor unit
PC board microcomputer
monitor (HAP) blinks.
NO
NO
NO
Operation
ready lamp (H2P) is
blinking.
Lamp does not
go off for 12 minutes or
more.
Is
indoor -
outdoor unit
transmission wiring
normal?
YES
The fuse F3U on
the outdoor unit's PC board is
burnt.
Replace outdoor unit PC
board (A1P).
YES
YES
Has
either the fuse
F4U on the outdoor
unit PC board (A1P) or the
fuse F1U on the inverter
PC board (A2P)
blown out?
NO
Are there
any broken wires in
the connectors of the inverter
PC board (A1P) and the
control PC board
(A2P)?
Reset the power supply.
YES
YES
YES
Supply 220~240 V.
NO
YES
NO
NO
NO
The
voltage between
terminals L3 and N of the
outdoor unit PC board is
220~240 V.
Is
resistance
between pins in excess of
judgment criteria?
Replace the fuse F4U and
the inverter PC board (A2P).
Replace the fan motor.
Replace the inverter PC
board (A2P).
Replace the fuse F4U.
Check No.3
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...