ESIE09-08A
Troubleshooting by Indication on the Remote Controller
Troubleshooting
167
3.19
“E5”
Indoor Unit: Inverter Compressor Motor Lock
Remote Control
Display
E5
Subcode 6
Applicable Models
All indoor units
Method of
Malfunction
Detection
Inverter PC board takes the position signal from UVW line connected between the inverter and
compressor, and the malfunction is detected when any abnormality is observed in the phase-current
waveform.
Malfunction
Decision Conditions
This malfunction will be output when the inverter compressor motor does not start up even in forced
startup mode.
Supposed Causes
Compressor lock (liquid suction (oil shortage))
High differential pressure (0.5MPa or more)
Incorrect UVW wiring
Faulty inverter PC board
Stop valve is left in closed.
Troubleshooting
Warning
: CAPACITOR SHOCK HAZARD. The capacitors (top surfaces) can hold up to 220V. Use
correct precautions when servicing.
Check the installation conditions.
Is
the stop valve
open?
NO
Is the UVW wiring
normal?
NO
NO
NO
NO
Is high
differential pressure
starting? (0.5MPa or
more)
YES
YES
YES
Check
and see whether
compressor is short-circuited
or ground.
YES
YES
Are inverter
output voltages the same
for 3 phases?
Does low
or high pressure
vary even instantaneously
when restarting
compressor?
YES
Caution
Be sure to turn off power switch before connecting or disconnecting
connector, otherwise parts may be damaged.
Open the stop valve.
Connect correctly.
Remedy the cause.
Replace the compressor.
Replace the inverter PC
board Assy.
Replace the compressor.
(V2793)
NO
Summary of Contents for ALTHERMA HT EKBUHAA6 V3
Page 2: ......
Page 7: ...ESIE09 08A Table of Contents v 1 3 Service Tools 283 Index i Drawings Flow Charts iii ...
Page 16: ...Model Names of Indoor Outdoor Units Tanks ESIE09 08A 4 General Information ...
Page 28: ...Refrigerant Circuit ESIE09 08A 16 Refrigerant Circuit EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 40: ...Functional Parts Layout ESIE09 08A 28 Refrigerant Circuit ...
Page 63: ...ESIE09 08A PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 Refrigerant Circuit 51 ...
Page 64: ...PCB Layout for EKHBRD 011 014 016 AA AB AC V1 Y1 ESIE09 08A 52 Refrigerant Circuit ...
Page 125: ...ESIE09 08A Field Setting Test Operation 113 ...
Page 232: ...Troubleshooting by Indication on the Remote Controller ESIE09 08A 222 Troubleshooting ...
Page 237: ...ESIE09 08A Piping Diagrams Appendix 227 EKHBRD 011 014 016 AB AC V1 Y1 ...
Page 250: ...Wiring Diagrams ESIE09 08A 240 Appendix EKHBRD 011 014 016 AB AC V1 ...
Page 251: ...ESIE09 08A Wiring Diagrams Appendix 241 ...
Page 256: ...Wiring Diagrams ESIE09 08A 246 Appendix EKHBRD 011 014 016 AB AC Y1 ...
Page 257: ...ESIE09 08A Wiring Diagrams Appendix 247 ...
Page 260: ...Wiring Diagrams ESIE09 08A 250 Appendix ...