Programming
3
Eight optically isolated, +24 V inputs are available at the Phoenix input connector under the right
side door and are defined as follows:
PIN 1
+24 VDC
PIN 2
Input 0
PIN 3
Input 1
PIN 4
Input 2
PIN 5
Input 3
PIN 6
Input 4
PIN 7
Input 5
Pin 8
Input 6
PIN 9
Input 7
PIN 10
Input Common
Pin 11
Signal Ground
Pin 12
Spare
Each of the physical inputs 0 - 7 can be programmed to have one of the following definitions:
Not Used
Unused
Tool Enable
When active, allows the tool to run in conjunction with Tool Start
Tool Start
Starts the tool. Works in parallel with the start switch on the tool.
Tool Reverse
When active, causes the tool to run in the counter-clockwise direc-
tion using the Backoff strategy. Works in parallel with the reverse
actuator on the tool
Tool Ready
Prepares the controller for a new rundown. When active, the previ-
ous outputs are cleared, and the yellow LEDs flash
Appl. Select 0
Application Selects 0-7 are used to select Applications 1-255
using a binary count of 0-254 where Appl. Select 0 is the
least significant bit. This feature overrides application
changes from the keypad. When Linking is activated, the
Tightening Group is selected with these inputs.
Appl. Select 1
Appl. Select 2
Appl. Select 3
Appl. Select 4
Appl. Select 5
Appl. Select 6
Appl. Select 7
Synchronization Input
If enabled from Advanced / System Settings, the tool is prevented
from continuing to the next stage until this input is active
Reset Linking
When active, Linking (batch counting) is reset to position one
Reject Release
Used when Reject Release is enabled from System Settings, and
the Release Method is "Release Input Toggle". When the tool is
disabled due to the reject limit being reached, it is re-enabled after
this input is toggled