4.
Connect the generator connector wires to the AC load center as follows:
a.
Route the generator connector wires up through the AC duct channel and behind the
AC load center.
b.
Feed the wires into the AC load center from behind, through the center entry hole on
the rear panel.
Note:
If any slack wires hang below the bottom edge of the load center, use cable ties to
secure the wires to the back of the rack beneath the load center.
c.
Terminate the generator connector wires to the load center as follows:
Connect the green wire to the ground bar.
Connect the white wire to the neutral bar.
Connect the black and red wires to the Gen. Conn. breaker.
5.
Replace the AC duct cover (two panels) and the AC load center cover panel.
6.
At the AC load center, switch all breakers to
ON
.
7.
At the local power transfer switch, restore AC power to the cabinet.