130
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2008 Calix. All Rights Reserved.
Cabinet
Type
# C7
Shelves
C7 Line Cards (Qty)
Max
1
Power
Required
# Rectifier
Modules Req’d
2
RPOTS
ADSL2
COMBO2
OLTG
HDSL2/4
20A
30A
ODC-3000
1
20
0
0
0
0
730 W
1
1
0
20
0
0
0
1230 W
2
1
0
0
20
0
0
1330 W
2
1
4
0
0
16
0
1150 W
1
1
0
0
0
0
20
1850 W
3
2
2
2
40
0
0
0
0
1460 W
2
1
0
40
0
0
0
2460 W
3
2
0
0
40
0
0
2660 W
3
2
8
0
0
32
0
2300 W
2
2
0
0
0
0
40
3700 W
3
4
3
Qtys below split
across
2 rectifier shelves
3
60
0
0
0
0
2190 W
3
2
0
60
0
0
0
3690 W
5
3
0
0
60
0
0
3990 W
5
3
12
0
0
48
0
3450 W
3
3
0
0
0
0
60
5550 W
3
6
5
4
80
0
0
0
0
2920 W
4
2
0
80
0
0
0
4920 W
6
4
0
0
80
0
0
5320 W
6
4
16
0
0
64
0
4600 W
4
4
0
0
0
0
80
7400 W
3
8
6
1
The maximum power values shown include a per-C7 minimum power load of 330 W, consisting of two RAP-OCn (2 x 65W), one
AMP (10W), one fan tray (70W), and one heat exchanger (120 W).
2
Calix recommends using an N+1 rectifier module scheme for redundancy. The quantity shown represents N only, with no
redundant module.
3
The max HDSL2/4 power values shown assume the max of 6 ports per card (HDSL2) configured to support line powering (DS1
Power = Source). However, in typical applications, 2 of the 20 cards would serve as standby units in 1:N protection schemes (two
1:9 groups).