c.
Push the ejector lever closed to secure the module in place.
3.
Repeat Steps 1 and 2 to replace additional rectifier modules.
As each rectifier module is installed, the shelf controller automatically identifies the new
module and configures the system. After all rectifier modules have been installed, the
controller displays
System OK
.
If a shelf controller fails, the system remains at the last known settings until a new controller
is installed.
To replace a Valere controller module
1.
Remove the installed controller module as follows:
a.
Grasp the top and bottom edges of the display face plate, then gently pull the face
plate down and forward to disconnect it from the controller module. Allow the face
plate to dangle.
b.
Loosen the set screw and slide the controller module halfway out of the slot.
c.
Disconnect the face plate's display cable from the controller module and set the face
plate aside.
d.
Disconnect the temperature probe, alarm, and expansion cables from the controller
module.
e.
Pull the controller module completely out of the shelf.
2.
Install a new controller module as follows:
a.
Insert the new controller module halfway into the slot.
b.
Reconnect the alarm, temperature probe, and expansion cables to the controller
module.
c.
Reconnect the face plate's display cable to the controller. Allow the face plate to
dangle.
d.
Push firmly on the module to seat it in the slot, then tighten the set screw.
e.
Re-attach the face plate to the controller module.
When the controller displays
System OK
, it has completed its initialization and is ready to
operate on default settings at the Basic Menu level.
Note:
For detailed instructions on controller functionality, including how to program the
controller module, see the
Valere Compact DC Power System Installation and Maintenance
manual.