123
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2008 Calix. All Rights Reserved.
Valere Rectifier Alarm Matrix
The Valere power shelf detects and reports multiple alarm conditions in the cabinet, but only
two umbrella alarms are reported through the C7: Rectifier Major (RECT/MJ) and Rectifier
Minor (RECT/MN). The following table lists the Valere alarms that may be reported by the
C7 as Rectifier Major or Rectifier Minor.
Alarm Condition
Display Severity
Major
Minor
AC Fail
X
High Voltage Warning
X
High Voltage Shut Down
X
Battery on Discharge
X
Any LVD Warning
X
Any LVD Open
X
Distribution Open
X
Redundant Capacity
X
Current Share
X
Single Rectifier Failure
X
Multiple Rectifier Failure
X
System Communication
X
High Temperature
X
Thermal Runaway (if T Comp is enabled)
X
Battery Test Failure
X