11
Proprietary Information: Not for use or disclosure except by written agreement with Calix.
© 2001-2008 Calix. All Rights Reserved.
Cabinet Features
Standard features of the ODC-3000 cabinet include:
Enclosure Design
Environmentally sealed design protects from dust and water intrusion
Compartmentalized for safety, including separate vented battery compartment
Separate splice chambers for copper and fiber entry (with AC on the fiber side)
Environmental and intrusion alarm systems
GR-487 compliant and UL-60950/UL-50 spec
Environmentally rated from -40C to +46C (per GR-487)
Equipment support
Swing out 23-inch front and rear equipment racks
108 RU total mounting space for equipment (27 RU per bay)
Door-mounted heat exchangers (4) provide 7400W of cooling capacity
Mechanical support for high density fiber and copper plant terminations
Modular, scalable copper line protection (50-pair block increments)
Power
220 VAC load center (UL-listed); 60 Amp capacity
AC service disconnect breaker
AC surge suppressor
Redundant AC supplies to DC power system
Convenience outlets (GFCI protected)
Valere compact DC power systems (2) with distribution
Redundant DC supplies to equipment (A and B)
Low voltage DC disconnect (-42V)
Up to 1020 Ah battery reserve capacity (NSB 170FT)