IEC / EN
61800-3
CISPR 11
Explanation
In this
document
Curves of limit
value
characteristic
Category C4
2
nd
environment
None
One of the following 3 requirements
must have been fulfilled:
●
Mains connection current > 400 A,
IT mains or required dynamic drive
behavior not reached by means of
EMC filter.
●
Adjust limit values to use and
operation on site.
●
User has to carry out and provide
evidence of EMC planning.
None
–
Category C3
2
nd
environment
Class A;
group 2,
I>100 A
Limit value in industrial areas to be
complied with for applications
operated at supply mains with
nominal current > 100 A
A2.1
1.1
1.2
Category C3
2
nd
environment
Class A;
group 2,
I≤100 A
Limit value in industrial areas to be
complied with for applications
operated at supply mains with
nominal current ≤ 100 A
A2.2
2.1
2.2
Category C2
1
st
environment
Class A;
group 1
Limit value in residential area or at
facilities at low-voltage mains
supplying buildings in residential
areas to be complied with
A1
3.1
3.2
Category C1
1
st
environment
Class B;
group 1
Limit value in residential areas to be
complied with
B1
4.1
4.2
Tab. 9-3: Limit values for line-based disturbances