Electric data of EMC filter for 3P 400 VAC models
Description
Symbol
Unit
0008-
A-05
0020-
N-05
Degree of protection according
to IEC 60529
–
–
IP 20
Listing according to UL stand-
ard (UL)
–
–
UL 1283
Listing according to CSA
standard (UL)
–
–
C22.2 No.8
Mass (weight)
m
kg
0.58
0.75
Mains voltage three-phase at
TN-S, TN-C, TT mains
U
LN
V
380…480
Mains voltage three-phase at
Corner- grounded-Delta mains
U
LN
V
Not allowed
Mains voltage three-phase at
IT mains
U
LN
V
Not allowed
Tolerance U
LN
(UL)
–
–
-15...+10 %
Input frequency (UL)
f
LN
Hz
50...60
Nominal current
I
L_cont
A
8
20
Calculation of leakage current
I
leak
mA
4.1
3.1
Required wire size according
to IEC 60364-5-52; at I
L_cont
A
LN
mm
2
4
5
Required wire size according
to UL 508 A (internal wiring);
at I
L_cont
(UL)
A
LN
AWG
10
10
Tab. 15-4: 3P 400 VAC electric data