Communication control register (0x7F00)
The address of command word register for communication control is 0x7F00.
This register is write-only. The frequency converter is controlled through writing
data into the address. The definition of each bit is shown in table below:
bit
Value
Description
15...8
–
Reserved
7
1
Control word active
0
Inactive
6
1
Stop Acc. / Dec. active (stop the internal Acc. / Dec. ramp generator)
0
Inactive
5
1
Fault reset active
0
Inactive
4
1
E-stop active
0
Inactive
3
1
Stop according to parameter setting
0
Inactive
2
1
Reverse
0
Forward
1
1
Jog active (jogging direction determined by bit 2)
0
Inactive
0
1
Run command active
0
Inactive
Tab. 14-24: Communication control register (0x7F00)
If the communication frame check is successful (CRC valid), the frequency con-
verter always accepts the content of the control word. All conflicts (e.g. run
command and stop command active at the same time) are resolved by the appli-
cation functionality (Run / Stop generator, jog control...). This assures that the
frequency converter will always react in the same manner, independent of the
run command source.