3-wire control mode 1
Step 1: Define 3 digital inputs
●
Set one of digital inputs as '35: Forward running (FWD)'
●
Set one of digital inputs as '36: Reverse running (REV)'
●
Set one of digital inputs as '25: 3-wire control'
To use 3-wire function, define the digital inputs first, and then activate the con-
trol mode. Otherwise, warning code 'PrSE' will be displayed on the operating
panel.
To deactivate the 3-wire function, deactivate the control mode first, and then de-
activate the function assignment of '25: 3-wire control'. Otherwise, warning
code 'PrSE' will be displayed.
Step 2: Activate 3-wire control 1
Set [E1.15] = '2: 3-wire control 1'.
Example:
Connected switch K1 to X1, and set [E1.00] = '35: Forward running (FWD)',
edge-sensitive.
Connected switch K2 to X2, and set [E1.01] = '36: Reverse running (REV)', level-
sensitive.
Connected switch K3 to X3, and set [E1.02] = '25: 3-wire control', level-sensitive.
Fig. 12-28: 3-wire control 1
The control logic is shown in the table below:
K3
K1
K2
Running status
Open
Inactive / Edge
Open / Closed
Stop
Open
Inactive / Edge
Open / Closed
Stop
Closed
Edge
Open
Running forward
Closed
Inactive / Edge
Closed
Running reverse
Tab. 12-9: 3-wire control configuration