12.5.3 Direction Control
Direction control via operation panel
The actual direction is controlled by the configuration of parameter [U0.00] 'Di-
rection control by panel' and [E0.17] 'Direction control'.
Code
Name
Setting range
Default
Min.
Attri.
U0.00 Direction control by panel
0: Forward
1: Reverse
0
–
Run
E0.17 Direction control
0: Forward / Reverse
1: Forward only
2: Reverse only
3: Swap default direction
0
–
Stop
[E0.17] setting
[U0.00] setting
Actual direction
0
Forward / Reverse
Forward
Forward
Reverse
Reverse
1
Forward only
Forward
Forward
Reverse
Converter stop and show error code 'dir1'
2
Reverse only
Forward
Converter stop and show error code 'dir2'
Reverse
Reverse
3
Swap default direction
Forward
Reverse
Reverse
Forward
Tab. 12-5: Direction configuration
For error codes 'dir1', 'dir2' concerning direction control, see
ter 13.4 "Error Code" on page 176
Reverse running frequency
Code
Name
Setting range
Default
Min.
Attri.
E0.11 Reverse running frequency
0.00...[E0.09] Hz
0.00
0.01
Stop
When the converter is running in reverse direction, the setting frequency will be
defined by E0.11.
This reverse running frequency is ONLY active when converter is NOT
running in multi-speed, simple PLC, or PID control mode.
VFC 3210
Bosch Rexroth AG
Functions and Parameters
DOK-RCON04-VFC3210****-IT01-EN-P
109/253