DC-braking during deceleration to stop
Code
Name
Setting range
Default
Min.
Attri.
E0.50 Stop mode
0: Decelerating stop
0
–
Stop
E0.52 Stop DC-braking frequency
threshold
0.00...50.00 Hz
0.00
0.01
Stop
E0.53 Stop DC-braking time
0.0...20.0 s (0.0: Inactive)
0.0
0.1
Stop
E0.54 Stop DC-braking current
①
0.0...150.0 %
0.0
0.1
Stop
E1.00 X1 input
16: Stop DC-braking activation
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
①
: percentage of frequency converter rated current.
'DC-braking to stop' can be activated in two ways:
●
by parameter settings
– [E0.50] = 0
– [E0.53] > 0
– [E0.54] > 0
– [Output frequency] ≤ [E0.52]
●
by digital inputs
– Any one of digital inputs is set to '16: Stop DC-braking activation'
– [E0.50] = 0
DC-braking starts when the defined digital input signal is active, and stops
when it is inactive. There is no time limitation.
VFC 3210
Bosch Rexroth AG
Functions and Parameters
DOK-RCON04-VFC3210****-IT01-EN-P
117/253