C1: Motor and system parameters
Code
Name
Setting range
Default
Min.
Attri.
C1.01 Motor parameter tuning
0: Inactive
1: Static auto-tuning
0
–
Stop
C1.02 Expert mode
0: Standard mode
1: Expert mode
0
–
Stop
C1.05 Motor rated power
0.1...1,000.0 kW
DOM
0.1
Stop
C1.06 Motor rated voltage
0...480 V
DOM
1
Stop
C1.07 Motor rated current
0.01...655.00 A
DOM
0.01
Stop
C1.08 Motor rated frequency
5.00...400.00 Hz
50.00
0.01
Stop
C1.09 Motor rated speed
1...60,000 rpm
DOM
1
Stop
C1.10 Motor rated power factor
0.00: Automatically identi-
fied
0.01...0.99: Power factor
setting
0.00
0.01
Stop
C1.12 Motor rated slip frequency
0.00...60.00 Hz
DOM
0.01
Stop
C1.20 Motor no-load current
0.00...[C1.07] A
DOM
0.01
Stop
C1.21 Stator resistance
0.00...200.00 Ω
DOM
0.01
Stop
C1.22 Rotor resistance
0.00...200.00 Ω
DOM
0.01
Stop
C1.23 Leakage inductance
0.00...200.00 mH
DOM
0.01
Stop
C1.24 Mutual inductance
0.0...3,000.0 mH
DOM
0.1
Stop
C1.25 Rotor leakage inductance
0.00...200.00
DOM
0.01
Stop
C1.69 Motor thermal model protection
setting
0: Inactive
1: Active
0
–
Stop
C1.70 Motor overload pre-warning level 100.0...250.0 %
100.0
0.1
Run
C1.71 Motor overload pre-warning delay 0.0...20.0 s
2.0
0.1
Run
C1.72 Motor thermal sensor type
0: PTC, KTY84/130
2: PT100; 3: PT1000
0
–
Stop
C1.73 Motor thermal sensor protection
level
0.0...10.0
2.0
0.1
Stop
C1.74 Motor thermal model protection
time constant
0.0...400.0 min
DOM
0.1
Stop
C1.75 Low speed derating frequency
0.10...300.00 Hz
25.00
0.01
Run
C1.76 Zero speed load
25.0...100.0 %
25.0
0.1
Run
VFC 3210
Bosch Rexroth AG
Appendix
DOK-RCON04-VFC3210****-IT01-EN-P
233/253