
Automatic start / stop according to setting frequency
With this function, the converter starts when the setting frequency from analog
input is higher than the threshold, and stops when the setting frequency from
analog input is lower than the threshold. The threshold is set by parameter
E0.41 'Automatic start / stop frequency threshold'.
To use this function, follow the rules below:
●
The frequency setting source should be set to analog inputs.
●
The first and second run command source should be set to '0: Panel'.
Code
Name
Setting range
Default
Min.
Attri.
E0.35 Starting mode
3: Auto start / stop accord-
ing to setting frequency
0
–
Stop
E0.41 Automatic start / stop frequency
threshold
0.01…[E0.09] Hz
16.00
0.01
Stop
E0.00 First frequency setting source
2: AI1 analog input
0
–
Stop
E0.02 Second frequency setting source
2
–
Stop
E0.01 First run command source
0: Panel
0
–
Stop
E0.03 Second run command source
1
–
Stop
Fig. 12-22: Automatic start or stop according to frequency threshold
●
When the setting frequency is higher than [E0.41], the frequency converter
starts and runs to the setting frequency automatically.
Bosch Rexroth AG
Functions and Parameters
VFC 3210
114/253
DOK-RCON04-VFC3210****-IT01-EN-P